Chapter 14 Fault Codes and DescriptionsC2000 Plus
14-34
ID* Display on LCD Keypad Fault Name Fault Descriptions
28
Under current
(uC)
Low current detection
Action and Reset
Action condition Pr.06-71
Action time Pr.06-72
Fault treatment parameter
Pr.06-73
0: No function
1: Fault and coast to stop
2: Fault and ramp to stop by 2
nd
deceleration time
3: Warn and operation continue
Reset method
Reset condition
Auto
When Pr.06-73 = 3, uC is a Warning”. The warning is
automatically
cleared when the output current > (Pr.06-71+0.1A).
Manual When Pr.06-73 = 1 or 2, uC is aFault. You must reset manually.
Record Reset immediately
Active level When Pr.06-71 = 1 or 2, uC is a “Fault”, and the fault is recorded.
Cause Corrective Actions
Motor cable disconnection Troubleshoot the connection between the motor and the load.
Improper setting of low-current
protection
Reset Pr.06-71, Pr.06-72 and Pr.06-73 to proper settings.
The load is too low
Check the load status.
Check if the motor capacity matches the load.