Chapter 14 Fault Codes and DescriptionsC2000 Plus
ID* Display on LCD Keypad Fault Name Fault Descriptions
61
Y-connection / Δ-
connection
switch fault
(ydc)
A fault occurs when
Y-Δ switches
Action and Reset
Action condition
1. ydc occurs when the confirmation signals of Y-connection and Δ-
are conducted at the same time.
2. If any of confirmation signals is not conducted within Pr.05-25, ydc occurs.
Action time Pr.05-25
Fault treatment parameter N/A
Reset method Manual reset
Reset condition
Can be reset only when the confirmation signal of Y-
connection is conducted if it
is Y-connection, or when the confirmation signal of Δ-
connection is conducted if
it is Δ-connection.
Record Yes
Cause Corrective Actions
The electromagnetic valve
operates incorrectly during Y-Δ
switch.
Check if the electromagnetic valve works normally.
If not, replace it.
Incorrect parameter setting Check if related parameters are all set up and set correctly.
The wiring of Y-Δ
incorrect
Check the wiring.