12 Descriptions of Parameter Settings | VFD-ED
12-01-7
Limit for Direct Docking Terminal
Control Mode
VF VFPG SVC FOCPG FOCPM
Default: 2.00
Settings 0.00–10.00
 Sets the limit for changing from leveling speed to acceleration when using terminals for direct docking.
Deceleration Distance for Direct Docking Terminal
Control Mode
VF VFPG SVC FOCPG FOCPM
Default: 30.00
Settings 0.00–10.00 cm
 Sets the distance between deceleration points.
Deceleration Distance Reference for Short Floor
Control Mode
VF VFPG SVC FOCPG FOCPM
Default: Read only
Settings 0.00–655.35 m
 Sets the distance between deceleration points according to short floors (write inhibit).
Short Floor/Direct Docking Terminal Enabled
Control Mode
VF VFPG SVC FOCPG FOCPM
Default: 0000h
Settings
0000h: Disabled
0001h: Short floor enabled
0002h: Direct docking terminal enabled
0003h: Short floor + direct docking terminal enabled
 Related parameters: Pr.02-01–02-08 multi-function input terminal (53: terminal leveling signal for direct
docking).
 Direct docking terminal function:
When the elevator runs to the leveling area, controller sends a leveling signal to the drive to make the
drive stop within effective distance (Pr.01-36). If deceleration distance is too short, the drive adjusts the
speed according to the limit for acceleration change (Pr.01-35). Deceleration of direct docking terminal
function is calculated through Pr.11-01.