Chapter 11 Summary of Parameter SettingsC2000-HS
11-17
Pr. Parameter Name Setting Range Default
03-18 Analog input addition function
0: Disable (AVI, ACI, AUI)
1: Enable
0
03-19
Signal loss selection for
analog input 4–20mA
0: Disable
1: Continue operation at the last frequency
2: Decelerate to 0Hz
3: Stop immediately and display ACE
0
03-20 Multi-function output 1 (AFM1) 0: Output frequency (Hz) 0
03-23 Multi-function output 2 (AFM2) 1: Frequency command (Hz) 0
2: Motor speed (Hz)
3: Output current (rms)
4: Output voltage
5: DC BUS voltage
6: Power factor
7: Power
8: Output torque
9: AVI
10: ACI
11: AUI
12: Iq current command
13: Iq feedback value
14: Id current command
15: Id feedback value
18: Torque command
19: PG2 frequency command
20: CANopen analog output
21: RS-485 analog output
22: Communication card analog output
23: Constant voltage output
25: CANopen and RS-485 analog output
03-21 Analog output gain 1 (AFM1) 0.0–500.0% 100.0
03-22
Analog output 1 in REV direction
(AFM1)
0: Absolute value of output voltage
1: Reverse output 0 V; forward output 0
10 V
2: Reverse output 5
0 V; forward output 510 V
0
03-24 Analog output gain 2 (AFM2) 0.0–500.0% 100.0
03-25
Analog output 2 in REV direction
(AFM2)
0: Absolute value of output voltage
1: Reverse output 0 V; forward output 0
10 V
2: Reverse output 5
0 V; forward output 510 V
0
03-27 AFM2 output bias -100.00–100.00% 0.00
03-28 AVI terminal input selection
0: 0–10V
1: 0–20mA
2: 4–20mA
0