Chapter 11 Summary of Parameter SettingsC2000-HS
11-26
06 Protection Parameters
Pr. Parameter Name Setting Range Default
06-00 Low voltage level
Frame D0–D: 300.0–440.0V
DC
Frame E and above: 380.0–440.0V
DC
360.0
400.0
06-01 Over-voltage stall prevention
0: Disabled
0.0–900.0V
DC
760.0
06-02
Selection for over-voltage stall
prevention
0: Traditional over-voltage stall prevention
1: Smart over-voltage stall prevention
0
06-03
Over-current stall prevention
during acceleration
0–160%
(100% corresponds to the rated current of the drive)
120
06-04
Over-current stall prevention
during operation
0–160%
(100% corresponds to the rated current of the drive)
120
06-05
Acceleration / deceleration time
selection for stall prevention at
constant speed
0: By current acceleration / deceleration time
1: By the 1
st
acceleration / deceleration time
2: By the 2
nd
acceleration / deceleration time
3: By the 3
rd
acceleration / deceleration time
4: By the 4
th
acceleration / deceleration time
5: By automatic acceleration / deceleration
0
06-06
Over-torque detection selection
(OT1)
0: No function
1: Continue operation after over-torque detection
during constant speed operation
2: Stop after over-torque detection during constant
speed operation
3: Continue operation after over-torque detection
during RUN
4: Stop after over-torque detection during RUN
0
06-07 Over-torque detection level (OT1)
10–250%
(100% corresponds to the rated current of the drive)
120
06-08 Over-torque detection time (OT1) 0.0–60.0 sec.
0.1
06-09
Over-torque detection selection
(OT2)
0: No function
1: Continue operation after over-torque detection
during constant speed operation
2: Stop after over-torque detection during constant
speed operation
3: Continue operation after over-torque detection
during RUN
4: Stop after Over-torque detection during RUN
0
06-10 Over-torque detection level (OT2)
10–250%
(100% corresponds to the rated current of the drive)
120
06-11 Over-torque detection time (OT2) 0.0–60.0 sec.
0.1
06-12 Current limit
0–170%
(100% corresponds to the rated current of the drive)
170