Chapter 11 Summary of Parameter SettingsC2000-HS
11-27
Pr. Parameter Name Setting Range Default
06-13
Electronic thermal relay selection
1 (Motor 1)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disable
2
06-14
Electronic thermal relay action
time 1 (Motor 1)
30.0–600.0 sec.
60.0
06-15
Temperature level over-heat (OH)
warning
0.0–110.0°C
105.0
06-16
Stall prevention limit level
(Weak magnetic area current stall
prevention level)
0–100% (Pr. 06-03, Pr. 06-04) 100
06-17
Fault record 1
(Present fault record)
0: No fault record
1: Over-current during acceleration (ocA)
0
06-18 Fault record 2 2: Over-current during deceleration (ocd) 0
06-19 Fault record 3 3: Over-current during constant speed (ocn) 0
06-20 Fault record 4 4: Ground fault (GFF) 0
06-21 Fault record 5 5: IGBT short-circuit (occ) 0
06-22 Fault record 6 6: Over-current at stop (ocS) 0
7: Over-voltage during acceleration (ovA)
8: Over-voltage during deceleration (ovd)
9: Over-voltage during constant speed (ovn)
10: Over-voltage at stop (ovS)
11: Low-voltage during acceleration (LvA)
12: Low-voltage during deceleration (Lvd)
13: Low-voltage during constant speed (Lvn)
14: Low-voltage at stop (LvS)
15: Phase loss protection (OrP)
16: IGBT over-heat (oH1)
17: Capacitance over-heat (oH2)
18: TH1 open: IGBT over-heat protection error (tH1o)
19: TH2 open: capacitance over-heat protection error
(tH2o)
21: Drive over-load (oL)
22: Electronics thermal relay protection 1 (EoL1)
23: Electronics thermal relay protection 2 (EoL2)
24: Motor overheat (oH3) (PTC / PT100)
26: Over-torque 1 (ot1)
27: Over-torque 2 (ot2)
28: Low current (uC)
29: Home limit error (LMIT)
30: Memory write-in error (cF1)