Chapter 11 Summary of Parameter SettingsC2000-HS
11-29
Pr. Parameter Name Setting Range Default
83: V phase output phase loss (OPHL)
84: W phase output phase loss (OPHL)
85: PG-02U ABZ hardware disconnection
86: PG-02U UVW hardware disconnection
87: oL3 Low frequency overload protection
89: RoPd Initial rotor position detection error
90: Inner PLC function is forced to stop
93: CPU error
101: CANopen software disconnect 1 (CGdE)
102: CAN open software disconnect 2 (CHbE)
104: CANopen hardware disconnect (CbFE)
105: CANopen index setting error (CIdE)
106: CANopen slave station number setting error
(CAdE)
107: CANopen index setting exceed limit (CFrE)
111: Internal communication overtime error (ictE)
112: PM sensorless shaft lock error
142: Auto-tuning error 1 (no feedback current error)
(AUE1)
143: Auto-tuning error 2 (motor phase loss error)
(AUE2)
144: Auto-tuning error 3 (no-load current I
0
measuring
error) (AUE3)
148: Auto-tuning error 4 (leakage inductance Lsigma
measuring error) (AUE4)
06-23 Fault output option 1 0–65535 (refer to bit table for fault code)
0
06-24 Fault output option 2 0–65535 (refer to bit table for fault code)
0
06-25 Fault output option 3 0–65535 (refer to bit table for fault code)
0
06-26 Fault output option 4 0–65535 (refer to bit table for fault code)
0
06-27
Electronic thermal relay selection
2 (Motor 2)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disable
2
06-28
Electronic thermal relay action
time 2 (Motor 2)
30.0–600.0 sec.
60.0
06-29
PTC detection selection / PT100
motion
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
0
06-30 PTC level / KTY84 Level 0.0–100.0%
50.0