Chapter 11 Summary of Parameter SettingsC2000-HS
11-30
Pr. Parameter Name Setting Range Default
06-31
Frequency command at
malfunction
0.0–1500.0 Hz
Read
only
06-32 Output frequency at malfunction 0.0–1500.0 Hz
Read
only
06-33 Output voltage at malfunction 0.0–6553.5 V
Read
only
06-34 DC voltage at malfunction 0.0–6553.5 V
Read
only
06-35 Output current at malfunction 0.0–6553.5 Amp
Read
only
06-36 IGBT temperature at malfunction -3276.7–3276.7°C
Read
only
06-37
Capacitance temperature at
malfunction
-3276.7–3276.7°C
Read
only
06-38 Motor speed at malfunction -32767–32767 rpm
Read
only
06-39 Torque command at malfunction -32767–32767 %
Read
only
06-40
Status of the multi-function input
terminal at malfunction
0000h–FFFFh
Read
only
06-41
Status of the multi-function output
terminal at malfunction
0000h–FFFFh
Read
only
06-42 Drive status at malfunction 0000h–FFFFh
Read
only
06-44 STO latch selection
0: STO latch
1: STO no latch
0
06-45
Treatment to output phase loss
protection (OPHL)
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
3
06-46
Detection time of output phase
loss
0.000–65.535 sec.
3.000
06-47
Current detection level for output
phase loss
0.00–100.00%
1.00
06-48
DC brake time of output phase
loss
0.000–65.535 sec.
0.000
06-49 LvX auto-reset
0: Disable
1: Enable
0
06-50
Time for input phase loss
detection
0.00–600.00 sec. 0.20