Chapter 11 Summary of Parameter SettingsC2000-HS
11-31
Pr. Parameter Name Setting Range Default
06-51 Capacitor oH warning level 0.0–110.0 degree
Depending
on the
model
power
06-52
Ripple of input phase loss 0.0–320.0V
DC
60.0
06-53
Detected input phase loss (OrP)
action
0: Warn and ramp to stop
1: Warn and coast to stop
0
06-55 Derating protection
0: Constant rated current and limit carrier wave by
load current and temperature
1: Constant carrier frequency and limit load current by
setting carrier wave
2: Constant rated current (same as setting 0), but
close current limit
0
06-56 PT100 voltage level 1 0.000–10.000 V 5.000
06-57 PT100 voltage level 2 0.000–10.000 V 7.000
06-58
PT100 level 1 frequency
protection
0.0–1500.0 Hz 0.0
06-59
PT100 activation level 1 protection
frequency delay time
0–6000 sec. 60
06-60
Software detection GFF current
level
0.0–6553.5 % 60.0
06-61 Software detection GFF filter time 0.00–655.35 sec. 0.10
06-62 dEb reset bias level 0.0–200.0 V
DC
40.0
06-63
Operation time of fault record 1
(Day)
0–65535 days
Read
only
06-64
Operation time of fault record 1
(Min.)
0–1439 min.
Read
only
06-65
Operation time of fault record 2
(Day)
0–65535 days
Read
only
06-66
Operation time of fault record 2
(Min.)
0–1439 min.
Read
only
06-67
Operation time of fault record 3
(Day)
0–65535 days
Read
only
06-68
Operation time of fault record 3
(Min.)
0–1439 min.
Read
only
06-69
Operation time of fault record 4
(Day)
0–65535 days
Read
only
06-70
Operation time of fault record 4
(Min.)
0–1439 min.
Read
only
06-71 Low current setting level 0.0–100.0 % 0.0
06-72 Low current detection time 0.00–360.00 sec. 0.00