Chapter 11 Summary of Parameter SettingsC2000-HS
11-34
Pr. Parameter Name Setting Range Default
when AC motor drive stops.
3: Fan turns ON when temperature (IGBT) reaches
around 60°C.
4: Fan always OFF
07-20
Emergency stop (EF) & force to
stop selection
0: Coast to stop
1: Stop by the 1
st
deceleration time
2: Stop by the 2
nd
deceleration time
3: Stop by the 3
rd
deceleration time
4: Stop by the 4
th
deceleration time
5: System deceleration
6: Automatic deceleration
0
07-21
Automatic energy-saving
selection
0: Disable
1: Enable
0
07-22 Energy-saving gain 10–1000% 100
07-23
Auto voltage regulation (AVR)
function
0: Enable AVR
1: Disable AVR
2: Disable AVR during deceleration
0
07-24
Torque command filter time
(V/F and SVC control mode)
0.001–10.000 sec. 0.500
07-25
Slip compensation filter time
(V/F and SVC control mode)
0.001–10.000 sec. 0.100
07-26
Torque compensation gain (V/F
and SVC control mode)
IM: 0–10 (when Pr. 05-33 = 0)
PM: 0–5000 (when Pr. 05-33 = 1 or 2)
0
07-27
Slip compensation gain (V/F and
SVC control mode)
0.00–10.00
0.00
(Default is
1.00 in SVC
mode)
07-29 Slip deviation level
0.0–100.0%
0: No detection
0
07-30
Over slip deviation detection
time
0.0–10.0 sec. 1.0
07-31 Over slip deviation treatment
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
0
07-32
Motor shock compensation
factor
0–10000
0: Disable
1000
07-33 Auto-restart interval of fault 0.0–6000.0 sec. 60.0
07-38
PMSVC voltage feedback
forward gain
0.50–2.00 1.00
07-62 dEb gain (Kp) 0–65535 8000
07-63 dEb gain (Ki) 0–65535 150