Chapter 12 Description of Parameter SettingsC2000-HS 
 
 
12.1-03-18 
 
 
Multi-function Output 1 (AFM1) 
 
 
    Default: 0 
 
 
Multi-function Output 2 (AFM2) 
 
 
  Default: 0 
  Settings 
0
–25 
Function Chart 
Settings  Functions  Descriptions 
0  Output frequency (Hz)  Maximum frequency Pr. 01-00 is regarded as 100%. 
1  Frequency command (Hz)  Maximum frequency Pr. 01-00 is regarded as 100%. 
2  Motor speed (Hz)  Maximum frequency Pr. 01-00 is regarded as 100%. 
3  Output current (rms)  (2.5 X rated current) is regarded as 100% 
4  Output voltage  (2 X rated voltage) is regarded as 100% 
5  DC BUS Voltage  450 V (900 V)=100% 
6  Power factor 
-1.000
–1.000=100% 
7  Power  (2 X rated power) is regarded as 100% 
8  Output torque  Full-load torque is regarded as 100% 
9  AVI 
0
–10V = 0–100% 
10  ACI 
4
–20mA = 0–100% 
11  AUI 
-10
–10V=0–100% 
12  Iq current command  (2.5 X rated current) is regarded as 100% 
13  Iq feedback value  (2.5 X rated current) is regarded as 100% 
14  Id current command  (2.5 X rated current) is regarded as 100% 
15  Id feedback value  (2.5 X rated current) is regarded as 100% 
18  Torque command  Rated torque is regarded as 100% 
19  PG2 frequency command  Maximum frequency Pr. 01-00 is regarded as 100%. 
20  CANopen analog output  CANopen communication analog output 
21  RS-485 analog output  For RS-485 (InnerCOM / MODBUS) control output 
22 
Communication card analog 
output 
Communication analog output (CMC-MOD01, 
CMC-EIP01, CMC-PN01, CMC-DN01) 
23  Constant voltage output 
Pr. 03-32 and Pr. 03-33 control voltage output level. 
0
–100 % of Pr. 03-32 corresponds to 0–10 V of AFM1.   
25 
CANopen and RS-485 analog 
output 
For CANopen and InnerCOM
 
control output 
 
 
 
Analog Output Gain 1 (AFM1) 
 
 
  Default: 100.0 
 
 
Analog Output Gain 2 (AFM2) 
 
 
  Default: 100.0 
  Settings  0.0–500.0 % 
 Adjusts the voltage level outputted to the analog meter from the analog signal (Pr.03-20) output 
terminal AFM of the drive.