Chapter 12 Description of Parameter SettingsC2000-HS 
 
12.1-03-19 
 
 
Analog Output 1 in REV Direction (AFM1) 
 
 
  Default: 0 
 
 
Analog Output 2 in REV Direction (AFM2)   
 
 
    Default: 0 
  Settings  0: Absolute value of output voltage 
    1: Reverse output 0 V; forward output 0–10 V 
    2: Reverse output 5–0 V; forward output 5–10 V 
 
 
 
AFM2 Output Bias 
 
 
  Default: 0.00 
  Settings  -100.00–100.00 % 
 Example 1, AFM2 0–10V is set to the output frequency, the output equation is:   
10V * (output frequency / Pr. 01-00) * Pr. 03-24 + 10V * Pr. 03-27 
 Example 2, AFM2 0–20mA is set to the output frequency, the output equation is: 
20mA * (output frequency / Pr. 01-00) * Pr. 03-24 + 20mA * Pr. 03-27 
 Example 3, AFM2 4–20mA is set to the output frequency, the output equation is: 
4mA + 16mA * (output frequency / Pr. 01-00) * Pr. 03-24 + 16mA * Pr. 03-27 
 This parameter sets the corresponding voltage for the analog output 0. 
 
 
AVI Terminal Input Selection 
 
 
  Default: 0 
  Settings  0: 0–10V 
1: 0–20mA 
2: 4–20mA 
 
 
 
ACI Terminal Input Selection 
 
 
  Default: 0 
  Settings  0: 4–20mA 
1: 0–10V 
2: 0–20mA 
 When  you  change  the  input  mode,  verify  that  the  external  terminal  switch  (SW3,  SW4) 
corresponds to the setting for Pr. 03-28–Pr. 03-29.