Chapter 1. Description of Hybrid Servo Drives | VFD-VJ
1-11
Air Flow
Model Heat Dissipation Rate (W)
Air Flow
Dissipation Rate
(CFM)
460V
Air
Cooled
VFD110VL43C-J
383.6 50
VFD150VL43C-J
404.1 50
VFD185VL43C-J
500.5 50
VFD220VL43C-J
580.9 50
VFD300VL43C-J
1037.8 133
VFD370VL43C-J
1078.7 133
VFD450VL43C-J
1370.1 209
VFD550VL43C-J
1536.5 209
The table above shows the required heat dissipation when installing a single drive in a confined
space.
When installing multiple drives, the required heat dissipation needs to be multiplied by the number
of drives.
The values of heat dissipation are calculated by rated voltage, rated current and default carrier
wave.