Chapter 12 Description of Parameter SettingsCP2000
12.1-06-16
Capacitance Temperature at Malfunction
Default: Read only
Settings -3276.7–3276.7°C
When a malfunction occurs, check the current capacitance temperature. If it happens again, it
overwrites the previous record.
Motor Speed in rpm at Malfunction
Default: Read only
Settings -32767–32767 rpm
When a malfunction occurs, check the current motor speed in rpm. If it happens again, it
overwrites the previous record.
Status of Multi-function Input Terminal at Malfunction
Default: Read only
Settings 0000h–FFFFh
Status of Multi-function Output Terminal at Malfunction
Default: Read only
Settings 0000h–FFFFh
When a malfunction occurs, check the status of multi-function input / output terminals. If it
happens again, it overwrites the previous record.
Drive Status at Malfunction
Default: Read only
Settings 0000h–FFFFh
When a malfunction occurs, check the current drive status (communication address 2101H). If it
happens again, it overwrites the previous record.
STO Latch Selection
Default: 0
Settings 0: STO latch
1: STO no latch
Pr.06-44=0: STO Alarm latch. After you clear the cause of the STO Alarm, use a Reset command
to clear the STO Alarm.
Pr.06-44=1: STO Alarm no latch. After you clear the cause of the STO Alarm, the STO Alarm
clears automatically.
All of STL1–STL3 errors are “Alarm Latch” mode (in STL1–STL3 mode, the Pr.06-44 function is
no effective).
Treatment to Output Phase Loss (OPHL)
Default: 3
Settings 0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning