3  Output current (A)  2.5 times of the rated current of the Hybrid servo 
drive is used as 100% 
4  Output voltage  2 times of the rated current of the Hybrid servo drive 
is used as 100% 
5  DC BUS voltage  450V (900V) =100% 
6 Power factor  -1.000~1.000=100% 
7  Power  Rated power of the drive =100% 
8  Output torque  Rated torque =100% 
9 PO  (0~10V=0~100%) 
10 PI  (0~10V=0~100%) 
11 AUI  (-10~10V=0~100%) 
12~20 Reserved 
 
 
 
Display the speed (rpm) defined by the user 
 
Control mode  VF  FOCPG  FOCPM   
  Factory default: 0 
 
Settings 0~39999 rpm 
  Set the maximum speed of the motor corresponding to the 100% flow. 
a 
 
Maximum value for the pressure command 
 
Control mode  VF  FOCPG  FOCPM   
  Factory default: 250 
 
Settings 0~250Bar 
  The 0~10V for the pressure command on the controller is mapped to 0~the value of this 
parameter. 
a 
 
Maximum pressure feedback value 
 
Control mode  VF  FOCPG  FOCPM   
  Factory default: 250 
 
Settings 0~400Bar 
  The 0~10V for the pressure sensor is mapped to 0~the value of this parameter. 
 
 
Pressure control mode 
 
Control mode  VF  FOCPG  FOCPM   
  Factory default: 0 
 
Settings  0: Speed control 
 
  1: Pressure control   
  This parameter determines the control mode of the Hybrid servo drive. It is recommended to use 
the speed control at the initial start up. After the motor, pump, pressure sensor, and the entire 
system are checked without any error, switch to the pressure control mode to enter the process 
control. 
 
 
Speed bandwidth 
 
Control mode   FOCPG  FOCPM   
  Factory default: 20 
 
Settings 0~40Hz 
  Set the speed response. The larger value indicates the faster response. 
a 
 
Pressure feedback filtering time PO