Chapter 12 Descriptions of Parameter SettingsMS300
446
Pr.
Parameter Name
Settings
01-07
Minimum output frequency of motor 1
Default setting
01-08
Minimum output voltage of motor 1
Default setting
01-12
Acceleration time 1
10 (sec.)
01-13
Deceleration time 1
10 (sec.)
01-24
S-curve for acceleration begin time 1
Default setting
01-25
S-curve for acceleration arrival time 2
Default setting
01-26
S-curve for deceleration begin time 1
Default setting
01-27
S-curve for deceleration arrival time 2
Default setting
03-00
Analog input selection (AVI)
1 (Frequency command)
03-28
AVI terminal input selection
Default setting
Setting 08: Textiles
The following table lists the relevant textile setting application parameters.
Pr.
Parameter Name
Settings
00-11
Speed control mode
0 (IMVF)
00-20
Master frequency command source
(AUTO, REMOTE)
1 (RS-485 communication input)
00-21
Operation command source
(AUTO, REMOTE)
1 (External terminals)
01-00
Motor 1 maximum operation frequency
Default setting
01-01
Rated / base frequency of motor 1
Default setting
01-02
Rated / base voltage of motor 1
Default setting
01-03
Mid-point frequency 1 of motor 1
Default setting
01-04
Mid-point voltage 1 of motor 1
Default setting
01-05
Mid-point frequency 2 of motor 1
Default setting
01-06
Mid-point voltage 2 of motor 1
Default setting
01-07
Minimum output frequency of motor 1
Default setting
01-08
Minimum output voltage of motor 1
Default setting
01-12
Acceleration time 1
10 (sec.)
01-13
Deceleration time 1
10 (sec.)
01-24
S-curve for acceleration begin time 1
0.2 (sec.)
01-25
S-curve for acceleration arrival time 2
0.2 (sec.)
01-26
S-curve for deceleration begin time 1
0.2 (sec.)
01-27
S-curve for deceleration arrival time 2
0.2 (sec.)
06-03
Over-current stall prevention during
acceleration
180 (%)
06-04
Over-current stall prevention during
operation
180 (%)
06-07
Over-torque detection level (motor 1)
200 (%)