Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-01-36
Super heavy duty 
           Control mode 
 
Models 
Default 
(kHz)  
VF 
SVC 
VFPG 
IMFOCPG 
IMTQCPG 
PMFOCPG 
PMTQCPG 
PMFOC 
IPMFOC 
IMFOC 
IMTQC 
SRMFOC* 
Settings (kHz) 
VFD007~110C23A/E 
VFD007~150C43A/E 
4  
2
–15 2–10 2–8 4–8 4–10 4–12 4–8 
VFD150~450C23A/E 
VFD185~550C43A/E 
4 
2–10 2–10 2–8 4–8 4–10 4–10 4–8 
VFD550~900C23A/E 
VFD750~3150C43A/E 
4  
2
–9 2–9 2–8 4–8 4–9 4–9 4–8 
VFD3550~5600C43A 
VFD3550~5600C43E 
3  
2
–9 2–9 2–8 4–8 4–9 4–9 4–8 
NOTE: In SRMFOC mode, the carrier frequency default is 4 kHz. 
 
Light duty / Normal duty / Heavy duty 
Models / Control mode 
VF, VFPG, SVC 
Settings (kHz)  Default (kHz) 
1~15HP (575V)  2–15  6 
20~600HP (690V)  2–9  4 
850HP (690V)  2–9  3 
 
 From the table, you see that the PWM carrier frequency has significant influences on the 
electromagnetic noise, the AC motor drive heat dissipation, and the motor acoustic noise. 
Therefore, if the surrounding noise is greater than the motor noise, lower the carrier frequency is 
good to reduce the temperature rise. Although it is quiet operation in the higher carrier frequency, 
the entire wiring and interference resistance should be considerate. 
 When Pr.00-11 = 8 (SynRM sensorless control), the maximum carrier frequency is 8 kHz. 
 When the carrier frequency is higher than the factory setting, it needs to protect by decreasing the 
carrier frequency. See Pr.06-55 for the related setting and details. 
 
00-19 
PLC Command Mask 
 
 
   
  Default: Read only 
 
 
Settings  bit0: Control command is forced by PLC control 
bit1: Frequency command is forced by PLC control 
bit2: Position command is forced by PLC control 
bit3: Torque command is forced by PLC control 
 Determine if the frequency command, control command or torque command is locked by PLC.