Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-02-27
  Status 2: After clearing a fault once a fault is detected and the external terminal for RUN stays   
ON, you can run the drive by pressing the RESET key. 
 
02-47 
Motor Zero-Speed Level 
 
 
   
 Default: 0 
 
 
Settings 0–65535 rpm 
 Use this parameter with the multi-function output terminals (set to 43). The motor needs to 
install encoder to feedback the actual rotating speed and use with PG card. 
 Use this parameter to set the level of motor at zero-speed. When the speed is lower than this 
setting, the corresponding multi-function output terminal that is set to 43 is ON (default), as shown 
below: 
 
 
02-48 
Maximum Frequency of Resolution Switch 
 
 
   
 
Default: 60.00 
 
 
Settings 0.00–599.00 Hz 
 
02-49 
Switch Delay Time of Maximum Output Frequency 
 
 
   
 
Default: 0.000 
 
 
Settings 0.000–65.000 sec. 
 Use this parameter to improve unstable speed or unstable position due to insufficient analog 
resolution. This function needs to be used with the external terminal (setting to 43). After setting 
this parameter, you also need to adjust the analog output resolution of the controller so as to 
work with the parameter function.