Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-08-9 
 
08-09 
Feedback Signal Fault Treatment 
 
 
   
 Default: 0 
 
 
Settings  0: Warn and continue operation 
1: Fault and ramp to stop 
2: Fault and coast to stop 
3: Warn and operate at last frequency 
  Valid only when the feedback signal is ACI (4–20 mA). 
  Set the treatments when the PID feedback signal is abnormal. 
 
08-10 
Sleep Level 
 
08-11 
Wake-Up Level 
 
 
   
 Default: 0.00 
 
 
Settings  0.00–599.00 Hz / 0.00–200.00% 
  Determine the sleep level, and if the sleep time and the wake-up level are enabled or disabled. 
Pr.08-10 = 0: Disabled; Pr.08-10 ≠ 0: Enabled. 
  When Pr.08-18 = 0, the unit for Pr.08-10 and that for Pr.08-11 switch to frequency. The settings 
are become 0.00–599.00 Hz. 
  When Pr.08-18 = 1, the unit for Pr.08-10 and that for Pr.08-11 switch to percentage. The settings 
are between 0.00–200.00%. 
  The percentage is based on the current command value, not the maximum value. For example, 
if the maximum value is 100 kg, and the current command value is 30kg, then if Pr.08-11 = 40%, 
the value is 12 kg. 
 
08-12 
Sleep Delay Time 
 
 
   
 Default: 0.0 
 
 
Settings 0.0–6000.0 sec. 
  When the frequency command is smaller than the sleep frequency and less than the sleep time, 
the frequency command is equal to the sleep frequency. However, the frequency command 
remains at 0.00 Hz until the frequency command becomes equal to or larger than the wake-up 
frequency. 
 
08-13 
PID Feedback Signal Error Deviation Level 
 
 
   
 Default: 10.0 
 
 
Settings 1.0–50.0% 
 
08-14 
PID Feedback Signal Error Deviation Detection Time 
 
 
   
 Default: 5.0 
 
 
Settings 0.1–300.0 sec. 
  When the PID control function is normal, it should calculate the value within a period of time that 
is close to the target value. 
  Refer to the PID control diagram for details. When executing PID feedback control, if |PID 
reference target value – detection value| > Pr.08-13 PID Feedback Signal Error Deviation Level 
and exceeds Pr.08-14 setting, it is regarded as a PID control fault, and the multi-function output 
terminal setting 15 (PID feedback error) activates.