Chapter 12 Description of Parameter SettingsC2000-HS
12.1-02-7
Settings Functions Descriptions
29
Signal confirmation for
Y-connection
When the control mode is V/F, ON: the drive operates by the first
V/F.
30
Signal confirmation for
-connection
When the control mode is V/F, ON: the drive operates by the
second V/F.
31 High torque bias
Refer to Pr. 11-30–Pr. 11-32 for details.
32 Middle torque bias
33
Low torque bias
34
Switch between
multi-step position and
multi-step speed control
ON: the corresponding 15-step speed for the multi-function
inputs 1
4 are 15 positions. Refer to Pr.04-16
Pr.04-44.
35
Enable single-point
position control
ON: the AC motor drive executes internal single-point position
control according to the setting for Pr.10-19. This function is valid
in FOCPG mode only.