Chapter 5 Main Circuit TerminalsC2000-HS
5-7
Frame D0
V/T2R/L1 T/L3 U/T1 W/T3S/L2
If you install at Ta 50°C environment, please select copper wire with voltage rating 600V and
temperature resistant at 75°C or 90°C.
If you install at Ta 50°C above environment, please select copper wire with voltage rating 600V and
temperature resistant at 90°C or above.
For UL installation compliant, please use copper wires for installation, the wire gauge is based on
temperature resistant at 75°C which is requested and recommended from UL. Do not reduce the
wire gauge when using higher temperature wire.
Model Name
Main Circuit Terminals
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, DC+, DC-
Terminal
Max. Wire
Gauge
Min. Wire
Gauge
Screw Spec. and
Torque (±10%)
Max. Wire
Gauge
Min. Wire
Gauge
Screw Spec. and
Torque (±10%)
VFD300C43S-HS
70mm
2
[2/0 AWG]
50 mm
2
[1/0 AWG]
M8
80kg-cm
[69.4 lb-in.]
[7.84Nm]
35 mm
2
[2 AWG]
25 mm
2
[4 AWG]
M8
80kg-cm
[69.4 lb-in.]
[7.84Nm]
VFD370C43S-HS
Frame D
T/L3 V/T2R/L1 U/T1 W/T3S/L2
If you install at Ta 50°C environment, please select copper wire with voltage rating 600V and
temperature resistant at 75°C or 90°C.
If you install at Ta 50°C above environmnet, please select copper wire with voltage rating 600V and
temperatrue resistant at 90°C or above.
For UL installation compliant, please use copper wires for installation, the wire gauge is based on
temperature resistnat at 75°C, which is requested and recommended from UL. Do not reduce the
wire gauge when using higher temperature wire.
Model Name
Main Circuit Terminals
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, DC+, DC-
Terminal
Max. Wire
Gauge
Min. Wire
Gauge
Screw Spec. and
Torque (±10%)
Max. Wire Gauge Min. Wire Gauge
Screw Spec. and
Torque (±10%)
VFD750C43A-HS
150mm
2
[300MCM]
150 mm
2
[300MCM]
M8
180kg-cm
[156.2 lb-in.]
[17.65Nm]
150mm
2
[300MCM]
95 mm
2
[3/0 AWG]
M8
180kg-cm
[156.2 lb-in.]
[17.65Nm]