Chapter 12 Description of Parameter SettingsC2000-HS
12.1-02-15
Settings Functions Descriptions
9 Drive is ready Active when the drive is ON with no error detected.
10 Low voltage warning (Lv)
Active when the DC BUS voltage is too low (refer to Pr. 06-00 Low
Voltage Level).
11 Malfunction indication Active when fault occurs (except Lv stop).
12
Mechanical brake
release (Pr. 02-32)
Active when the drive runs after the set delayed time for Pr. 02-32.
This function must use with DC brake function.
13
Over-heat warning (Pr.
06-15)
Active when IGBT or heat sink overheats; to prevent the drive
from shutting down due to over-heating (refer to Pr. 06-15).
14
Software brake signal
indication
Active when the soft brake function is ON (refer to Pr. 07-00) .
15 PID feedback error Active when the PID feedback signal error is detected.
16 Slip Error (oSL) Active when the slip error is detected.
17
Count value reached,
does not return to 0 (Pr.
02-20)
When the drive executes external counter, this contact is active if
the count value is equal to the setting value for Pr. 02-20.
This contact is not active when the setting value for Pr. 02-20 > Pr.
02-19.
18
Counter value reached,
returns to 0 (Pr. 02-19)
When the drive executes the external counter, this contact is
active if the count value is equal to the setting value for Pr. 02-19.
19
External interrupt B.B.
input (Base Block)
Active when external interrupt (B.B.) stop output occurs in the
drive.
20 Warning output Active when a warning is detected.
21 Over-voltage Active when over-voltage is detected.
22
Over-current stall
prevention
Active when over-current stall prevention is detected.
23
Over-voltage stall
prevention
Active when over-voltage stall prevention is detected.
24
Operation mode
indication
Active when the operation command is controlled by external
terminal. (Pr. 00-21≠0)
25 Forward command Active when the operation direction is forward.
26 Reverse command Active when the operation direction is reverse.
27
Output when Current ≥
Pr. 02-33
Active when the current is ≥ Pr. 02-33.
28
Output when Current <
Pr. 02-33
Active when the current is < Pr. 02-33
29
Output when frequency
≥ Pr. 02-34
Active when the frequency is ≥ Pr. 02-34.
(Actual output H ≥ Pr.02-34)
30
Output when Frequency
< Pr. 02-34
Active when the frequency is < Pr. 02-34.
(Actual output H < Pr.02-34)