4-32
a
Low voltage level
Control mode VF FOCPG FOCPM
Factory default: 180/360
Settings 230V Series: 160 – 220V
460V Series: 320 – 440V
This parameter is used to set the LV discrimination level.
LV
02-07
Input Voltage
30V(60V)
a
PTC action selection
Control mode VF FOCPG FOCPM
Factory default: 0
Settings 0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
Parameter 02-08 is used to define the operation mode of the drive after the PTC is activated.
a
PTC level
Control mode VF FOCPG FOCPM
Factory default: 50.0
Settings 0.0~150.0%
0.0~150.0
This parameter defines the maximum value of the analog input for 100% of the activation level of
the PTC.
a
PTC detection filtering time
Control mode VF FOCPG FOCPM
Factory default: 0.20
Settings 0.00 – 10.00 seconds
a
PTC type
Control mode VF FOCPG FOCPM
Factory default: 0
Settings 0: Not assigned
1: KTY84
When this parameter is set as 1, the unit for Parameters 02-09 and 02-12 will be changed from %
to °C.
a
Motor fan activation level
Control mode VF FOCPG FOCPM
Factory default: 50.0
Settings 0.0~100.0%
0.0~150.0