Chapter 12 Description of Parameter SettingsC2000-HS 
 
12.1-00-17 
 
 
Operation Command (HAND) Source 
  
 
  Default: 0 
  Settings  0: Digital keypad 
    1: External terminals 
    2: RS-485 serial communication 
    3: CANopen communication card 
    5: Communication card (does not include CANopen card) 
  Determines the operation frequency source in HAND mode. 
  Use Pr.00-20 and Pr.00-21 to set the frequency source and the operation source in AUTO mode, 
and use Pr.00-30 and 00-31 to set the frequency source and the operation source in HAND 
mode. Select or switch AUTO / HAND mode by using the digital keypad KPC-CC01 or setting the 
multi-function input terminal MIx = 41, 42. 
  The default for the frequency source and operation source is for AUTO mode. It returns to AUTO 
mode whenever you cycle the power. If you use a multi-function input terminal to switch AUTO / 
HAND mode, the multi-function input terminal has the highest priority. When the external terminal 
is OFF, the drive does not accept any operation signal and cannot execute JOG. 
 
 
Digital Keypad STOP Function 
  
 
  Default: 0 
  Settings  0: STOP key disable 
    1: STOP key enable 
  This parameter is valid when the digital keypad is not set as the operation command source (Pr. 
00-21≠0). When Pr. 00-21=0, the STOP key on the digital keypad is not affected by this 
parameter. 
 
 
Homing mode 
  
   
  Default: 0000h 
  Settings: 
 
Note: Forward run = clockwise (CW) 
     Reverse run = counterclockwise (CCW) 
    X  0: Forward run to home. Set PL forward limit as checkpoint.     
1: Reverse run (CCW) to home. Set NL reverse limit (CCWL) as 
checkpoint. 
2: Forward run to home. Set ORG: OFF→ON as checkpoint. 
3: Reverse to home. Set ORG: OFF→ON as checkpoint. 
4: Forward run and search for Z-pulse as checkpoint. 
5: Reverse run and search for Z-pulse as checkpoint. 
6: Forward run to home. Set ORG: ON→OFF as checkpoint. 
7: Reverse run to home. Set ORG: ON→OFF as checkpoint. 
8: Define current position as home.