Chapter 12 Description of Parameter SettingsC2000-HS 
 
 
12.1-01-6 
 
 
JOG Acceleration Time 
 
 
JOG Deceleration Time 
  
 
  Default: 10.00 
  Settings  Pr. 01-45 = 0: 0.00–600.00 seconds 
    Pr. 01-45 = 1: 0.00–6000.0 seconds 
 Use the acceleration time to determine the time required for the AC motor drive to accelerate 
from  0.0  Hz  to  maximum  output  frequency  (Pr.  01-00).  The  Deceleration  Time  is  used  to 
determine  the  time  required  for  the  AC  motor  drive  to  decelerate  from  the  Maximum  Output 
Frequency (Pr. 01-00) down to 0.00Hz. 
 The acceleration and deceleration time are invalid when using Pr. 01-44 Auto-acceleration and 
Deceleration Setting. 
 Select the acceleration and deceleration time 1, 2, 3, and 4 with the multi-function input terminals 
settings. The defaults are acceleration and deceleration time 1. 
 With  the  enabled  torque  limits  and  stall  prevention  functions,  the  actual  acceleration  and 
deceleration time are longer than the above action time. 
 Note  that  setting  the  acceleration  and  deceleration  time  too  short  may  trigger  the  protection 
function (Pr. 06-03 Over-current Stall Prevention during Acceleration or Pr. 06-01 Over-voltage 
Stall Prevention).   
 Note  that  setting  the  acceleration  time  too  short  may  cause  motor  damage  or  trigger  drive 
protection due to over-current during acceleration.   
 Note  that  setting  the  deceleration  time  too  short  may  cause  motor  damage  or  trigger  drive 
protection due to over-current during deceleration or over-voltage. 
 Use suitable brake resistors (refer to Chapter 07 Optional Accessories) to decelerate in a short 
time and prevent over-voltage. 
 When you enable Pr. 01-24–Pr. 01-27 (S-curve acceleration and deceleration begin and arrival 
time), the actual acceleration and deceleration time are longer than the setting. 
 
 
 
JOG Frequency 
  
 
  Default: 6.0 
  Settings  0.0–1500.0 Hz 
 You can use both the external terminal JOG and F1 key on the keypad KPC-CC01 to set the JOG 
function. When the JOG command is ON, the AC motor drive accelerates from 0 Hz to the JOG 
frequency (Pr. 01-22). When the JOG command is OFF, the AC motor drive decelerates from the 
JOG frequency to stop. The JOG acceleration and deceleration time (Pr. 01-20, Pr. 01-21) are the 
time to accelerate from 0.0Hz to the JOG frequency (Pr. 01-22). You cannot execute the JOG 
command when the AC motor drive is running. When the JOG command is executing, other 
operation commands are invalid.