Chapter 12 Description of Parameter SettingsC2000-HS 
 
12.1-01-7 
 
 
First / Fourth Acceleration / Deceleration Frequency 
 
 
  Default: 0.0 
  Settings  0.0–1500.0 Hz 
 This function does not require the external terminal switching function; it switches the 
acceleration and deceleration time automatically by the Pr.01-23 setting. If you set the external 
terminal, it is based on the external terminal first, and not on Pr.01-23. 
 When using this function, and the fourth acceleration time is set too short, set the S-curve 
acceleration time to 0.   
a.  When Pr. 01-02 = 10s, Pr. 01-18 = 6s, then the 0–40 Hz acceleration time is 3s and 40–80 Hz 
acceleration time is 5s. 
b.  When Pr. 01-13 = 8s, Pr. 01-19 = 2s, then the 80–40 Hz deceleration time is 4s and 40–0 Hz 
deceleration time is 1s. 
 
 
S-curve Acceleration Begin Time 1 
 
S-curve Acceleration Arrival Time 2 
 
 
S-curve Deceleration Begin Time 1 
 
 
S-curve Deceleration Arrival Time 2 
  
 
  Default: 0.20 
  Settings  Pr. 01-45=0: 0.00–25.00 seconds 
    Pr. 01-45=1: 0.0–250.0 seconds 
 Sets a slow start when the drive begins to accelerate at the start. The acceleration and 
deceleration curve adjust the S-curve acceleration and deceleration according to the parameter 
value. When you enable this function, the drive has a different acceleration and deceleration 
curve based on the acceleration and deceleration time. 
 The S-curve function is disabled when you set the acceleration and deceleration time to 0. 
 When Pr. 01-12, Pr. 01-14, Pr. 01-16, Pr. 01-18  Pr. 01-24 and Pr. 01-25, the actual acceleration 
time = Pr. 01-12, Pr. 01-14, Pr. 01-16, Pr. 01-18 + (Pr. 01-24 + Pr. 01-25) / 2 
 When Pr. 01-13, Pr. 01-15, Pr. 01-17, Pr. 01-19  Pr. 01-26 and Pr. 01-27, the actual deceleration 
time = Pr. 01-13, Pr. 01-15, Pr. 01-17, Pr. 01-19 + (Pr. 01-26 + Pr. 01-27) / 2