Chapter 12 Description of Parameter SettingsCP2000 
 
 
12.1-03-20 
 
 
AFM2 Output Selection 
 
 
AFM1 Output Selection 
 
 
  Default: 0 
  Settings  0: 0–20 mA output 
1: 4–20 mA output   
 
 
 
AFM1 DC Output Setting Level 
 
 
AFM2 DC Output Setting Level 
 
 
  Default: 0.00 
  Settings  0.00–100.00% 
  Pair with multi-function output: 23, Pr.03-32 and Pr.03-33 outputs constant AFM voltage. 
 
Set Pr.03-32 between 0–100.00% to correspond to 0–10 V of AFM1. 
 
Set Pr.03-33 between 0–100.00% to correspond to 0–10 V of AFM2. 
 
AFM1 Filter Output Time 
 
AFM2 Filter Output Time 
 
 
  Default: 0.01 
  Settings  0.00–20.00 sec. 
 
 
 
Multi-function MO Output by AI Level Source 
 
 
  Default: 0 
  Settings  0: AVI1 
1: ACI   
2: AVI2 
 
 
AI Upper Level   
 
 
  Default: 50.00 
  Settings  -100.00–100.00% 
 
 
AI Lower Level   
 
 
  Default: 10.00 
  Settings  -100.00–100.00% 
 Multi-function output terminal “67” must work with Pr.03-44 to select input channels. When analog 
input level is higher than Pr.03-45, multi-function output acts; when analog input level is lower 
than Pr.03-46, multi-function output terminals stop outputting. 
 When setting levels, AI upper level must be higher than AI lower level. 
 
 
Analog Input Curve Selection   
 
 
  Default: 7 
  Settings  0: Regular Curve 
    1: Three-point curve of AVI1 
    2: Three-point curve of ACI 
    3: Three-point curve of AVI 1& ACI   
    4: Three-point curve of AVI2