Chapter 12 Description of Parameter SettingsCP2000   
 
 
12.1-07-6 
to zero speed. If the power recovers at this time, the drive restarts the motor after the dEb return 
time. 
   Lv return level: Default value depends on the drive power model 
Frame A, B, C, D = Pr.06-00 + 60V/30V (230V models)   
Frame E and above = Pr.06-00 + 80V/40V (230V models)   
  Lv level: Default = Pr.06-00 
  During dEb operation, other protection such as ryF, ov, oc, occ and EF may interrupt it, and 
these error codes are recorded. 
  The STOP (RESET) command does not work during the dEb auto-deceleration, and the drive 
continues  decelerating  to  stop.  To  make  the  drive  coast  to  stop  immediately,  use  another 
function (EF) instead. 
  The B.B. function does not work when executing dEb. The B.B. function is enabled after the dEb 
function finishes. 
  Even though the Lv warning does not display during dEb operation, if the DC bus voltage is 
lower than the Lv level, MOx = 10 (Low voltage warning) still operates. 
  The following explains the dEb action: 
When the DC voltage drops below the dEb setting level, the dEb function start to work (soft start 
relay remains closed) and the drive executes auto-deceleration. 
  Situation 1:  Momentary  power-loss, or power current too low and  unstable, or  power  supply 
sliding down because of sudden heavy load. 
Pr.07-13=1,  “dEb  active,  DC  bus  voltage  returns,  output  frequency  does  not  return”  and 
power recovers. When the power recovers and DC bus voltage exceeds the dEb return level, 
the drive linearly decelerates to 0 Hz and stops. The keypad displays the ”dEb” warning until 
you manually reset it, so that you can see the reason for the stop.