Chapter 12 Description of Parameter SettingsCP2000 
 
 
12.1-09-13 
 
 
Block Transfer 8 
 
 
Block Transfer 9 
 
 
Block Transfer 10 
 
 
Block Transfer 11 
 
 
Block Transfer 12 
 
 
Block Transfer 13 
 
 
Block Transfer 14 
 
 
Block Transfer 15 
 
 
Block Transfer 16 
 
 
  Default: 0000 
  Settings  0–FFFFh 
  There  is  a  group  of  block  transfer  parameters  available  in  the  AC  motor  drive  (Pr.09-11  to 
Pr.09-26). Using communication code 03H, you can store the parameters (Pr.09-11–Pr.09-26) 
that you want to read.
 
  For example: according to the Address List (as shown in the table below), Pr.01-42 is shown as 
012A. Set Pr.09-11 to 012Ah (the minimum voltage of Pr.01-42 M2 is 2.0 V), and use Pr.09-11 
(communication address 090B) to read the communication parameter, the read value is 2.0.
 
AC motor drive 
parameters 
GGnnH 
GG is the parameter group, nn is the parameter number; for 
example, the address of Pr.04-10 is 040AH. 
 
 
Communication Decoding Method   
 
 
  Default: 1 
  Settings  0: Decoding Method 1 (20xx) 
    1: Decoding Method 2 (60xx) 
 
  Decoding Method 1  Decoding Method 2 
Source of 
Operation 
Control 
Digital Keypad  Digital keypad controls the drive action regardless of decoding method 1 or 2. 
External Terminal  External terminal controls the drive action regardless of decoding method 1 or 2. 
RS-485  Refer to address: 2000h–20FFh  Refer to address: 6000h–60FFh 
CANopen  Refer to index: 2020-01h–2020-FFh  Refer to index: 2060-01h–2060-FFh 
Communication Card  Refer to address: 2000h–20FFh  Refer to address: 6000h–60FFh 
PLC  PLC commands controls the drive action regardless of decoding method 1 or 2. 
 
 
 
Internal Communication Protocol 
 
 
  Default: 0 
  Settings  1: BACnet 
    0: Modbus 485 
    -1: Internal Communication Slave 1 
    -2: Internal Communication Slave 2 
    -3: Internal Communication Slave 3 
    -4: Internal Communication Slave 4 
    -5: Internal Communication Slave 5