Chapter 12 Descriptions of Parameter SettingsMS300 
302 
 
Signal confirmation 
for Y-connection 
When the control mode is V/F, ON: the drive operates by the 
first V/F. 
Signal confirmation 
for -connection 
When the control mode is V/F, ON: the drive operates by the 
second V/F. 
Refer to Pr.11-30–11-32 for details. 
Disable writing 
EEPROM function 
(parameters 
memory disable) 
ON: writing to EEPROM is disabled. Changed parameters are 
not saved after power off. 
For torque control (Pr.00-10 = 2), when the torque command is 
AVI or ACI, ON: negative torque. 
ON: during operation, the motor coasts to stop. 
1.  When the MI terminal switches to OFF, it executes a STOP 
command. Therefore, if the MI terminal switches to OFF 
during operation, the drive stops. 
2.  Use the optional keypad KPC-CC01 to switch between 
HAND and AUTO. The drive stops first, and then switches 
to HAND or AUTO status. 
3.  The optional digital keypad KPC-CC01 displays the current 
status of the drive (HAND / OFF / AUTO). 
Mechanical gear 
ratio switch 
ON: the mechanical gear ratio switches to the second group. 
Refer to Pr.10-04–Pr.10-07 for details. 
When the drive is enabled, the RUN command is valid. 
When the drive is disabled, the RUN command is invalid.   
When the drive is operating, the motor coasts to stop. 
This function varies with MO = 45. 
Slave dEb action to 
execute 
Enter the message setting in this parameter when the master 
triggers dEb. This ensures that the slave also triggers dEb, then 
the master and slave stop simultaneously.