What causes Input Voltage Out of Range on Det-Tronics X Series Security Sensors?
- VVanessa MannSep 12, 2025
The input voltage is not within 18Vdc to 30Vdc. Check the power supply and input power wiring.
What causes Input Voltage Out of Range on Det-Tronics X Series Security Sensors?
The input voltage is not within 18Vdc to 30Vdc. Check the power supply and input power wiring.
What to do if my Det-Tronics Security Sensors display RTC Fault?
Set the RTC via the Flame Inspector Software. If the fault is reoccurring return to the factory.
What to do if my Det-Tronics X Series Security Sensors display RTC Error?
Set the RTC via the Flame Inspector Software. If the fault is reoccurring return to the factory.
What to do if my Det-Tronics X Series display Temperature Out of Range?
Relocate detector or provide a shield from the heat source.
How to resolve UV Manual oi Fault on Det-Tronics Security Sensors?
Clean detector windows and oi reflector plate. Re-initiate manual Optical Integrity (oi) test. Calibrate oi if the detector does not return to normal status.
How to resolve IR Manual oi Fault on Det-Tronics Security Sensors?
Clean detector windows and oi reflector plate. Re-initiate manual Optical Integrity (oi) test. Calibrate IR oi if the detector does not return to normal status.
What to do if my Det-Tronics Security Sensors display oi Calibration Failed?
Clean the detector windows and oi reflector plate. If a successful calibration cannot be achieved, return the unit to the factory.
What to do if my Det-Tronics Security Sensors display Manual oi Test at Booth Fault?
Check the Manual Optical Integrity terminals and wiring for a potential short or activation.
How to fix Software Manual oi Test Failed on Det-Tronics X Series Security Sensors?
Clean the detector windows and oi reflector plate. Calibrate Optical Integrity if Optical Integrity returns are not within +/- 5% of 100%.
How to fix Hardware Manual oi Test Failed on Det-Tronics X Series Security Sensors?
Clean the detector windows and oi reflector plate. Calibrate Optical Integrity if Optical Integrity returns are not within +/-5% of 100%.
Provides a general description of the Det-Tronics Enhanced Flame Inspector Software.
Lists the key capabilities and functionalities of the software.
Specifies the necessary computer hardware for running the Enhanced Flame Inspector software.
Details the hardwired and alternate methods for installing the software and connecting to detectors.
Details how to install the Enhanced Flame Inspector software onto a computer.
Guides the user through the initial startup process and establishing communication with the detector.
Details software configuration options for various X-Series flame detector models.
Explains how to view and interpret detector status indicators and information.
Explains how to determine and change detector configuration and programming settings.
Guides on how to check the current operational status of the detector.
Details manual oi test procedures initiated by magnet, switch, or software.
Illustrates the control screen layouts for different X-Series detector models, showing test and calibration options.
Provides step-by-step instructions for performing optical integrity (oi) calibration on detectors.
Details the procedure for testing and calibrating the detector's 4-20 mA output signal.
Explains how to access, view, and manage detector event logs and their data.
Covers sorting event logs and saving them for external analysis.
Refers to detailed descriptions of event log entries found in subsequent sections of the manual.
Provides event log descriptions and troubleshooting advice for X3301 and X3302 detectors.
Provides event log descriptions and troubleshooting advice for X2200, X5200, and X9800 detectors.
Information on obtaining replacement parts for the detectors and software.
Details on how to order the software, kits, and related accessories.
| Detection Principle | Infrared (IR) |
|---|---|
| Housing Material | Stainless Steel |
| Power Supply | 24 VDC |
| Outputs | 4-20 mA, HART |
| Enclosure Rating | IP66/67 |
| Approvals | ATEX, IECEx, FM, CSA, SIL 2 (depending on model) |
| Certifications | CSA (depending on model) |