Deutronic DBL Manual (MPC4) - 14VDC - EN - 11 / 20 - 10 / 2006
Parameter Value Setting range / Information
Max. battery
charge capacity
(in Ampere hours)
Q
max
0 to 6000 Ah (Q
max
= typ. 250 Ah)
SAFETY FUNCTION - stops charging!
Hint for a full charge of the battery:
Adjust the limit for battery charging capacity in the setup more then about
20% higher as the nominal value given by the battery manufacturer
Min. charging
time
T
min
0 to 240 Minutes (T
min
= typ. 15 min)
Time interval after which the charger is allowed to switch back to trickle
charge
Max. charging
time
T
max
0,1 to 99 Hours (T
max
= typ. 24 hours)
SAFETY FUNCTION - stops charging!
Parameter Value Setting range / Information
FEATURES: BVL: ON / OFF
Signal ‘battery full’ activated / deactivated
Ibvl
Current limit, at which the signal ‘battery full’ is indicated via LED or via a
connected external signal lamp (Ibvl = typ. 12,0 A)
Note: Signalization of ‘battery full’ state is independent from any trickle
current limit
SHORTCELL:
DETECT ON /
OFF
Definition / explanation – see 7) Annex – CELLCHECK / SHORT CELL
DETECT