Page 27
RCCD 1
RCCD 2
MCB
Compressor &
controller
In line flow boiler
+
DHW immersion switched
by heat pump
In line flow boiler
+
DHW immersion switched
by a relay controlled by the
heat pump or no DHW
immersion installed
Total running
current
(Amps)
Suggested
„type C‟
MCB
rating
LA 6 MI
21A
26A
13A
47
50
34
50
LA 9 MI
23A
26A
13A
49
50
36
50
RCCD 1
RCCD 2
RCCD 3
MCB
Compressor
& controller
In line flow
boiler
DHW immersion
switched by
heat pump
DHW immersion switched
by a relay controlled by
the heat pump or no DHW
immersion installed
Total running
current
(Amps)
Suggested
„type C‟ MCB
rating
LA 12 MI
25A
26A
13A
0A
51
63
64
80
LA 16 MI
27A
26A
13A
53
63
66
80
Table 14: Calculation of running current for entire heat pump to size power supply cable and MCB at distribution
board.