EasyManua.ls Logo

Distech Controls Allure EC-Smart-Vue Series - Subnetwork Bus Specifications

Distech Controls Allure EC-Smart-Vue Series
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 / 16
Subnetwork Bus Total Length
The total maximum length of all Subnetwork buses, including both the length of the Allure Series Communicating Sensor Subnetwork bus and the
ECx-400 Series Subnetwork bus is 300 m (1000 ft). The maximum length of the Allure Series Communicating Sensor Subnetwork bus is 200 m (650 ft).
The maximum length of the ECx-400 Series Subnetwork bus is 300 m (1000 ft).
Sub-Network Bus Total Length: 300 m (1 000 ft) Maximum
Sub-Network Bus: 200 m
(650 ft) Maximum
Allure EC-Smart-Vue
Sub-Network Bus: 300 m
(1 000 ft) Maximum
ECx-400
Typical Compatible
Controller
Extension I/O Modules
ECx-400
Sub-Network Bus - Cat 5e Cable
with RJ-45 Connectors
Allure EC-Smart-Vue
Sub-Network Bus
ECx-400
2-Wire Shielded Cable
Figure5: Subnetwork Bus Overview Showing the Allure EC-Smart-VueSubnetwork Bus and the ECx-400 Series Subnetwork Bus.
A controller can support a maximum of two Allure EC-Smart-Vue sensor models equipped with a CO
2
sensor; the remaining connected models must be
without a CO
2
sensor. See Table 1 for the quantity of room devices supported by each controller model.
For instance, if the controller model supports a subnetwork with 12 Allure EC-Smart-Vue sensors in total, then 10 sensor models must be without a CO2
sensor and the other two can be equipped with a CO2 sensor. To ensure proper operation, it is recommended to distribute the sensors throughout the
length of the subnetwork.
Cat 5e Cable with RJ-45 Connectors
Sub-Network Bus Total Length: 1 000 ft (300 m) Maximum
10x...2x...
Bus: 600 ft (180 m) Maximum
Allure EC-Smart-Vue
Sensor Sub-network
ECB-600 ECL-600or
Typical
Controller
ECx-400
Sub-Network Bus
Figure6: Allure EC-Smart-Vue Sensor Subnetwork Length and Distribution
For ECB/ECL-PTU Series controllers, the maximum length between two consecutive devices on the sub-network bus
is 100 feet (30 m).

Table of Contents

Related product manuals