Calibration Verification
4-30 72A-1230 Rev. F
July 22, 2005
Test Date: 06/29/95
Test Time: 10:14:45
System Serial Number = 59400175
Test Fail: 3mA SinTheta = -0.045979%
Final Error Code = 00-00-0-04H
End of Test
Test Date: 04/03/96
Test Time: 14:33:16
System Serial Number = 59400175
Final Error Code = 00-00-00-00H
End of Test
Test Date: 04/26/96
Test Time: 10:48:42
System Serial Number = 59400175
Test Abort: Error #53
Test Not Running -
One or Both Low Voltage Leads Disconnected
Final Error Code = 00-00-00-00H
End of Test
Test Date: 04/26/96
Test Time: 10:50:43
System Serial Number = 59400175
Test Abort: Error #53
Test Not Running -
One or Both Low Voltage Leads Disconnected
Final Error Code = 00-00-00-00H
End of Test
Figure 4.9 Example of Calver.log File Contents
Additional data are continually added to the file by each subsequent
Calibration Verification. The print option, if selected at the end of a test, prints
only results from the test just completed.
When a failure is encountered, Doble can provide troubleshooting guidance if
needed. A copy of the Calver.log file, found in the DTA directory, is essential.