RMD10 Troubleshooting
39
RMD10.5T, RMD10.5XT
Faults are caused by a fault code with a warning symbol ( ) in the middle of the
display.
Reset ERROR type faults manually:
➤ Press the control knob for 2 seconds.
✓ A beep sounds.
✓ The error has been reset.
RMD10.5, RMD10.5X
In the event of a fault, the LED warning symbol (
) in the display lights up
continuously and the LEDs flash according to the fault.
Reset ERROR type faults manually:
➤ Press the button for 2 seconds.
✓ A beep sounds.
✓ The error has been reset.
Fault messages
Code LEDs Fault Typ e Solution
W01
Temperature sensor in the
refrigerator compartment
defective
Warning Replace the temperature
sensor.
E03 No connection between
power module and
display
Error Check the connection
between the power
module and display.
Reset the error manually.
W05 AC power not connected
or AC voltage < 190 V
Warning Connect the refrigerator to
AC or select a different
energy type, e.g. gas or
DC.
W06 DC power not connected Warning Connect the refrigerator to
DC or select a different
energy type, e.g. gas or
AC.