Fig.7 - Refrigeration Line Sizes
Notes:
Maximum length of refrigerant line between condensing unit and
cooling unit is 50 feet (15m).
Only use seamless refrigeration grade copper tubing.
Insulate discharge and suction tubes separately.
Use minimum 3/8” (10mm) thick closed cell insulation.
Seal (glue and/or tape) all insulation seams.
Use “dead-head” orientation of TEEs on multiple cooling unit sys
-
tems to help ensure proper distribution of refrigerant.