13.2 System Control Specifications
13.3 System Inputs
Set point operating range: 18.3 °C to 29.4 °C (65 °F to 85 °F)
Ambient temperature operating range
displayed:
–15 °C to 65.6 °C (5 °F to 150 °F)
Sensor accuracy: ±1.1 °C at 25 °C (± 2 °F at 77 °F)
Low voltage limit 230 V units: 175 Vw
Low voltage processor reset: 50 Vw
Line voltage: 230 Vw
Frequency: 50 Hz
Fan output (max.): 6 A at 230 Vw
Valve output: 0.25 A at 230 Vw
Heater output (max.): 20 A at 230 Vw
Pump output: 1/2 HP at 230 Vw
Compressor output: 2 HP at 230 Vw
Minimum operating temperature: –17.8 °C (0 °F)
Maximum ambient operating temperature: 82.2 °C (180 °F)
Maximum Rh conditions: 99 % Non Condensing
Display power consumption < 5 W
Ambient or inside air temperature: 1
High pressure switch, HPF: 1
Low pressure switch, LPF
(Not used in MCST):
1
Alternate inside air temperature sensor: 1
Outside air temperature sensor (optional): 1