EasyManuals Logo

Dometic MCS T6 User Manual

Dometic MCS T6
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
EN
MCS T6, MCS T12, MCS T16 Technical data
37
13.2 System Control Specifications
13.3 System Inputs
Set point operating range: 18.3 °C to 29.4 °C (65 °F to 85 °F)
Ambient temperature operating range
displayed:
–15 °C to 65.6 °C (5 °F to 150 °F)
Sensor accuracy: ±1.1 °C at 25 °C (± 2 °F at 77 °F)
Low voltage limit 230 V units: 175 Vw
Low voltage processor reset: 50 Vw
Line voltage: 230 Vw
Frequency: 50 Hz
Fan output (max.): 6 A at 230 Vw
Valve output: 0.25 A at 230 Vw
Heater output (max.): 20 A at 230 Vw
Pump output: 1/2 HP at 230 Vw
Compressor output: 2 HP at 230 Vw
Minimum operating temperature: –17.8 °C (0 °F)
Maximum ambient operating temperature: 82.2 °C (180 °F)
Maximum Rh conditions: 99 % Non Condensing
Display power consumption < 5 W
Ambient or inside air temperature: 1
High pressure switch, HPF: 1
Low pressure switch, LPF
(Not used in MCST):
1
Alternate inside air temperature sensor: 1
Outside air temperature sensor (optional): 1
MCS-6-12-16--O-West.book Seite 37 Dienstag, 14. November 2017 11:28 11

Other manuals for Dometic MCS T6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dometic MCS T6 and is the answer not in the manual?

Dometic MCS T6 Specifications

General IconGeneral
BrandDometic
ModelMCS T6
CategoryAir Conditioner
LanguageEnglish

Related product manuals