Operating MCS T6, MCS T12, MCS T16
8
6.2 Dual Button Functions
Up and Down Buttons
While in the On Mode: Simultaneously press the Up and Down Buttons to dis-
play outside air temperature providing the optional outside air temperature sen-
sor is installed.
While in the Program Mode: Simultaneously press the Up and Down Buttons
to set new program defaults.
Power and Down Buttons
While viewing the service fault history log: Simultaneously press the Power
and Down Buttons to clear the fault history log (see “Service History Log” on
page 14).
While in the On Mode: Simultaneously press the Power and Down Buttons to
enter the Dehumidification Mode (see “Dehumidification Mode” on page 11).
7Operating
7.1 Initial startup
A
Ensure seawater intake ball valve (seacock) is open.
Turn on air conditioner circuit breaker.
If the seawater pump has its own circuit breaker, turn that on.
Press the Fan Button (fig. 1 2, page 3).
This energizes the fan.
Verify that the fan is running and that there is steady airflow out of the supply-air
grille.
Select a temperature set point lower than the current cabin temperature.
This starts the compressor and seawater pump.
NOTICE!
Do not turn the unit off and immediately turn it back on. Allow at least
30 s for refrigerant pressure equalization.