[CHAPTER 6 FUNCTION TABLE & DESCRIPTION]
6-18 |
DOOCHPUMP
dr-21 Motor Stopping Method
ㆍ It sets motor stopping method
Setup Data Functional Description
Related Function
0 (Factory Setting) Decelerated Stop
dr-23 Falling Time
To cut off drive output voltage 1
dr-22 Rising Time
ㆍ It is time to reach max frequency from 0[Hz].
ㆍ If rising time is too short, over- current fault may be occurred during motor operation.
Factory Setting Input Range
1.0~600.0[sec] 3.0[sec]
dr-23 Falling Time
ㆍ It is time to decelerate to 0[Hz] from max frequency.
ㆍ If falling time is too short, over- voltage fault may be occurred during motor operation
Factory Setting Input Range
1.0~600.0[sec]6.0[sec]
dr-30 Overload Trip Selection
ㆍ It sets up whether it will generate trip upon overload of the motor.
ㆍ It is used for protecting the motor.
Setup Data Functional Description
Release 0
Related Function
dr-12 Rated Current of Motor
dr-31 Overload Trip Level
1 (Factory Setting) Setting
dr-32 Overload Trip Time
dr-20 Motor Rotation Direction Selection
ㆍ It sets up rotation direction of the pump.
ㆍ Be sure to check the rotation direction of the pump for normal operation.
As the rotation direction may change according to wiring, be sure to check it.
Setup Data Functional Description
0 (Factory Setting) Forward Direction– CW(Clockwise)
Reverse - CCW(Counterclockwise)1