HY-DP-MANUAL-001 20
• Alarm will be activated when the gearbox oil temperature is
1bar or lower
• It is normal when the boost air pressure is between 1.1bar
and 2.9bar
*Boost Air Pressure (Low)
• Alarm will be activated when the boost air pressure is 1bar
or lower
*Boost Air Pressure (High)
• Alarm will be activated when the boost air pressure is 3bar
or higher
• Alarm will be activated when the engine oil temperature is
150℃ or higher
Exhaust Air Temperature
(High)
• Alarm will be activated when the exhaust air temperature is
600℃ or higher
• Alarm will be activated when the coolant level is 30% or
lower
• Alarm will be activated when the fuel level is 30% or lower
- It identifies the status of spare sensor, product S/N, F/W version, and date/time. Press button
of the function key to move to spare sensor page.
3. Part Names, Operation and Settings
[Fig. 3-25] Spare Sensor and SW information
[Table 3-11] Spare Sensor Conditions