14/16
RZN 43xx-E
99.821.70 3.5/01/12
Please check following points, if the smoke vent system fails to function satisfactorily or the green control LED in the button fails to lighten. Diagnosis must be
carried out in following order: 1st supply plug-in card VE, 2nd line plug-in card LE, 3rd group plug-in card GE, 4th window lock plug-in card AE, 5th smoke
detector and external control. Detected faults must be eliminated at once before the diagnosis is continued!
Trouble shooting
To test the function of the earth fault checkup, the diagnosis pins on the VE must be bridgeover.
If the LED does not light, it might be necessary to check the grounding and connect it correctly.
Symptoms
Supply plug-in card VE
Line plug-in card LE
Group plug-in card
Window-lock plug-in card
Smoke detector
External control
LED diode lightens.
LED diode lightens
LED diode fails to lighten
LED diode lightens
LED diode lightens.
LED diode lightens.
LED diode fails to lighten.
LED diode lightens.
LED diode lightens.
Pilot light extinguishes during closing
operation of drive, red LED diode
lightens, flap can't be closed.
Pilot light extinguishes during opening
operation of drive after approx. 20 seconds,
red LED diode lightens.
LED diode lightens.
LED diode lightens.
LED diode fails to lighten.
LED diode lightens.
LED diode fails to lighten.
Detector cannot be reset, though
there is no smoke existing.
Detector fails to respond, when
checked with smoke.
Smoke vent is opens without external alarm;
smoke vent can be reset again.
Smoke vent opens without external alarm.
Smoke vent cannot be reset again.
Smoke vent is not opening, though external
system gives alarm.
.
.
.
GE
AE
Remedy
Eliminate earth fault.
Check accumulator, connection and fuse.
Call in-house electrician immediately for eliminating
power failure.
Connect line.
.
1. Bridge diagnostic pin against middle pin on line
plug-in card.
Check fuse, connections, cables, t ,
clamps, smoke detectors and external control.
2. Bridge diagnostic pin against middle pin on line
plug-in card.
Check fuses, connections, cables, terminal resistors,
terminals and smoke vent buttons.
Check fuses, connections, cables, and t
on drive.
Check t or terminal module between
terminal and .
Check t or terminal module between
terminal and .
.
1. Bridge diagnostic pin against middle pin
on plug-in card
Check fuses, connections, cables, t ,
terminals, smoke detectors and external control.
2. Bridge diagnostic pin against middle pin
on plug-in card.
Check fuses, connections, cables, t ,
terminals and smoke vent buttons.
Check fuse, terminals and loop resistance.
Exchange detector.
Exchange detector.
In case of repetition, disconnect contact.
Search for fault in external system.
Disconnect temporary perhaps, so that the
smoke vent remains operative.
Search for interruption; check whether
contact in external system is really closing.
For exact diagnosis proceed as follows
57
56
For diagnosis proceed as follows
erminal resistor
erminal resistor
erminal resistor
erminal resistor
erminal resistor
erminal resistor
Causes
Earth fault.
Malfunction in accumulator
No 230V power supply available.
Line is disconnected
Malfunction in smoke detector or
smoke vent button line.
Malfunction in smoke detector line.
Malfunction in smoke vent button line.
Malfunction in group
Malfunction in group
Malfunction in group
Malfunction in plug-in card.
Malfunction in smoke detector line .
Malfunction in smoke vent button line
Malfunction in line to magnetic valve.
Detector is dirty or faulty.
Defector is faulty or wrong type.
External system gives possibly only short
contact by malfunction or has given alarm or
false alarm and has been unknown reset
again.
Ensure, that contact in external system is
opened. If external alarm is not resettable by
malfunction, search there for malfunction.
Main contact is not closing
.
.
.
.
.
RM
RT.
OK
OK