15
Alert Setting for Temperature(all models)
Time delay setting of temperature buzzer alarm(Atb)
Atb=60 min
time
Atu=30
buzzer
ON
When the relative temperature is higher than 30
,
buzzer will be activated from Hb to Hc.
Hb
Ha
HcHc
Time delay
Set Atb
Step 1
Press and hold ▼, then press SET.
Step 2
Press to select from
t→AtuAtFAtb. Choose Atb.
Step 3
Press ▲ or ▼ to reach the required time delay of 60 minutes.
Step 4
Press SET to store the setting.