EasyManua.ls Logo

Dräger REGARD 2400 - Intended Use; Product Description; Product Features

Dräger REGARD 2400
34 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
Intended Use
Product Description
Product Features
2. Intended Use
The Dräger REGARD 2400 / 2410 is used to monitor combustible, toxic, and/or other gases
and to control alarm signals, display units and other devices via alarm relays.
3. Product Description
Dräger REGARD 2400 / 2410 is a freely programmable controller unit for the connection of
up to four transmitters. Gases of different types can be monitored. The unit can be operated
with 1 or 2 alarm thresholds. Depending on the version, Dräger REGARD 2400 / 2410 provi-
des up to six relays. Four of these can be set according to the customer requirements; two
relays are fixed - one for activating an acoustic alarm (e.g. horn) and one for indicating fault
conditions.
4. Product Features
Suitable for DIN rail mounting or wall mounting
Supply voltage 24 VDC / 110 VAC / 230 VAC
Up to four 4...20 mA transmitter or Pellistor sensing heads
1 fault signal via relay
1 horn contact via relay
Up to 2 alarm signals via relays
Up to 2 freely adjustable alarm thresholds
Latching, hysteresis or pulse outputs
Display of current gas reading
Test function for output relays
Line-break and short-circuit monitoring of sensor wiring
1 reset button for horn and alarms
LEDs for alarm, horn and fault
Communication port for optional modules
2 digital inputs
DANGER
Dräger REGARD 2400 / 2410 must not be used and is not approved for use in areas where
flammable and explosive gas mixtures may occur. Danger of explosion!