STEAM INJECTION
Humidifiers
Installation, Operation,
and Maintenance Manual
READ AND SAVE THESE INSTRUCTIONS
For use with steam boilers

Questions and Answers

  • M
    Monica SinghAug 31, 2025
    How to fix a DriSteem SINGLE-TUBE Humidifier that leaks water?
    • D
      Daniel BensonAug 31, 2025
      If your DriSteem Humidifier is leaking water, the cause could be: * Defective O-rings on the tube adapter. Replace the O-rings. * A steam leak in the outer jacket of the dispersion tube. Repair the leak, or replace the tube. Ensure the tubes are not rigidly anchored to allow for thermal expansion.
  • C
    Crystal BrockNov 10, 2025
    Why is my DriSteem SINGLE-TUBE Humidifier discharging water in the duct?
    • S
      sharon95Nov 10, 2025
      If the DriSteem Humidifier discharges water in the duct, it could be due to several reasons: * The steam main might be overloaded with water because the boiler is discharging water with steam, or the steam main dripping is improper. You should locate the cause of priming and correct it. * The steam trap may not be draining properly. Try replacing, repairing, or cleaning the trap as required and reduce the back pressure of the condensate return line. * The steam pressure might be too low (below 2 psi [14 kPa]). Verify that steam shutoff valves are fully open, adjust the pressure reducing valve, and adjust the boiler pressure. * Condensate might be collecting in low, undripped points in the steam main. Install drips and steam traps as required. * Steam jacketing of the tube is not...
  • B
    Benjamin NorrisNov 20, 2025
    What to do if humidity exceeds setting on DriSteem SINGLE-TUBE Humidifier?
    • S
      Samantha MontgomeryNov 20, 2025
      If the humidity exceeds the humidistat setting in your DriSteem Humidifier, here are a few potential causes and solutions: * The automatic valve may not be fully closing. This could be due to foreign matter holding the valve open (clean the valve and check the line strainer), a broken valve spring (replace the spring), valve stem packing adjusted too tightly (loosen or replace the packing), steam pressure exceeding the close-off rating of the valve spring (replace the actuator or valve spring), the valve being installed backwards (remount it), or the valve linkage needing adjustment (adjust the valve linkage). * The control system might be malfunctioning. Check for incorrect control voltage, signal, or improper wiring, and correct as necessary. Also, verify and correct if the humidity...