PowerSeries Neo Installation Guide
SIA Feature Programming
Section
Comments Range/Default Requirement
Exit Time
[005]>[001], option 3
Access to Entry and Exit delays and Bell Time Out for the system. Range:45- 255
seconds
Default: 60 sec.
Required
(programmable)
Exit Delay Restart
[018], option 7
Opening a Delay zone door after it has already been opened and closed during an exit delay restarts the
exit delay timer.
Default: Enabled Required
Auto Stay Arm on Un-vacated
Premises
[001]>[001]-[128] Zone type 05,
06,09
Function key: Forces the system to arm in Stay mode if the occupant does not exit the premises after
pressing the Away function key.
If no exit after full
arm
Default: Enabled
Required
Exit Time and Progress
Annunciation/Disable or Remote
Arming
[861]>[001]-[005], option 4
System times and audible exit beeps can be disabled when using the wireless key to stay arm the system.
When away arming, audible exit beeps can not be disabled.
Default: Enabled Allowed
Entry delay(s)
[005]>[001]-[008], options 1 and 2
Access to entry and exit delays and bell time out for the system
Note: Combined entry delay and communications delay (abort window) shall not exceed 60s.
Range: 30 sec. to 4
min.
Default: 30 sec.
Required
(programmable)
Abort Window for Non-Fire zones
[002]>[001]-[128], option 7 ON
Access to zone attributes, i.e., swinger shutdown, transmission delay and cross zone. May be disabled by
zone or zone type.
Default: Enabled Required
Abort Window Time - for Non-
Fire zones
[377]>[002], option 1
Access to the programmable delay before communicating alarms
Note: Combined entry delay and communications delay (abort window) shall not exceed 60 seconds.
Range: 00 - 45 sec.
Default: 30 sees
Required
(programmable)
Abort Annunciation An audible tone is generated when an alarm is aborted during the abort window. Hard-coded ON Required
Duress Feature
[*][5]> master code> user 2-95> 5>
2
When this feature is enabled, selected user codes send a duress reporting code to the central station when
used to perform any function on the system. Section [019], option [6] must be enabled.
Default: N Required
Cancel Window
[377]>[002], option 6
Access to the communications cancel window. Minimum duration must be 5 minutes. Range: 005-255
Default: 005
Cancel Annunciation
[308]>[001], option 8
Access to the reporting code for Alarm Canceled. A Cancel was
transmitted
Default: Enabled
Required
Cross Zoning
[042]>Selection 3, option 002
Enables cross zoning for entire system. Zones can be enabled for cross zoning via zone attribute option
8 in sections [002][101] - [128].
Programming
required
Default: Disabled
Required
Burglary Verification Timer
[005]>[000], option 3
Access to the programmable Cross Zone timer. Range: 000-255 sec.
Default: 60 seconds
Allowed
Swinger Shutdown for Alarms
[377]>[001], option 1
Access to the swinger shutdown limit for zone alarms
For all non-fire zones, shut down at 1 to 6 trips.
Default: 2 trips Required
(programmable)
Swinger Shutdown Enable
[002]>[001] - [128], option 6 ON
Access to swinger shutdown, transmission delay and cross zone attributes. Zone attribute option 6
(Swinger Shutdown enabled) is ON.
Non-police response
zones
Default: Enabled
Allowed
24-Hr. Auto-verified Fire
[001]>[001]-[128], Zone type 025
ON
Access to 24-Hr. Auto-verified Fire
Activates if Not restored within the specified time.
Must choose zone
type for application
Required
Call Waiting Cancel
[382], option 4 OFF
Access to the dialing sequence used to disable call waiting. Call waiting string can be programmed in
[304]
Depends on user
phone line
Default: Disabled
Required
System Test:
[*][6] Master Code, option 04
The system activates all keypad sounders, bells or sirens for 2 seconds and all keypad lights turn on.
Refer to user manual (part no. 29008365).
Walk Test Mode:
[*][8][Installer code][901]
This mode is used to test each zone on the system for proper functionality.
Walk Test Communications
[382], option 2
Enables communication of zone alarms while walk test is active. Default: Disabled
Walk Test Start/ End Reporting
Codes
[308][401], options 1 and 2
Access to the reporting codes for walk test start and end times.
- 27 -