PowerSeries Neo Installation Guide
Bell Output:
l 12V, 700mA supervised (1k Ohm) bell output (current limited at
2 amps)
l Steady, Pulsed, Temporal 3 fire, CO alarm cadences
l Bell short detection (software + hardware)
Aux+:
l Voltage range = 9.6V - 13.8V DC
l Current = 700mA (shared with PGM outputs)
l Output ripple voltage: 270mVp-p max.
l Onboard programmable outputs:
l PGM 1 - 50mA switched programmable output
l PGM 2 - 300mA current-limited switched programmable
output. 2-Wire smoke detectors (90mA current limited)
are supported using this PGM
l PGM 3 - 50mA switched programmable output
l PGM 4 - 50mA switched programmable output
l Hardware PGM over current protection
Battery
l 12V sealed lead acid, rechargeable
l Battery capacity:
l 4Ah (PS4-12)
l 7Ah (BD7-12)
l 14Ah
l Maximum standby time: 24 hours (with 14Ah battery and Aux
current limited to 470mA)
l Recharging time to 80% 72 hours
l Recharging rate: 240mA (12 hours max.), 480mA (24 hour
backup)
l Backup time: 24 hours (UL)
l Battery lifespan: 3-5 years
l Low battery trouble indication threshold 11.5VDC
l Battery restore voltage 12.5V
l Main board current draw (battery only):
l HS2016/32/64/128 (no alternate communicator) standby
85mA DC
l HS2016/32/64/128, (including alternate communicator)
standby 190mA DC
l Transmit (alternate communicator module) 195mA DC
l Resettable fuses (PTC) used on circuit board
l Supervision for loss of primary power source (AC fail), battery
loss or battery low voltage (battery trouble) with indication
provided on the keypad
l Internal clock locked to AC power frequency
Operating Environmental Conditions
l Temperature range: UL= 0°C to +49°C (32°F-120°F),
l Relative humidity: <93% non condensing
Alarm Transmitter Equipment (ATE) Specification
l Digital dialer integral to the main control board
l Supports SIA and Contact ID
l Complies with TS203 021-1, -2, -3 Telecom equipment require-
ments and EN50136-1-1, EN50136-2-1, EN50136-2-3 ATS 2
l Optional Dual IP/Cellular communicators (3G2080(R)/ TL2803G
(R)/ TL280(R)) can be installed in the same enclosure and con-
figured as primary or back-up, with AES 128-bit encryption
l Compliant with EN50136-1-1, EN50136-2-1 ATS2 requirements
System Supervision Features
The PowerSeries Neo continuously monitors a number of possible trouble
conditions and provides audible and visual indication at the keypad.
Trouble conditions include:
l AC power failure
l Zone trouble
l Fire trouble
l Telephone line trouble
l Communicator trouble
l Low battery condition
l RF jam
l AUX power supply fault
l Failure to communicate
l Module fault (supervisory or tamper)
Additional Features
l 2-way wireless device support
l Visual verification (images + audio)*
l Proximity tag support
l PGM scheduling
l Quick arming
l User, partition, module, zone and system labels
l Soak test*
l Programmable system loop response
l Keypad and panel software versions viewable through keypad
l Doorbell zone type
l Low battery PGM type
*Feature not evaluated by UL/ULC.
- 10 -