43
REPORTINGV CODES
Section
#
Reporting Code Code Sent When... Dialer
Direction*
Auto-
matic
Contact
ID
SIA Auto
Rep
Codes**
[344-348]
Openings system disarmed (user 01-34, 40-42 indicated) O/C (4) A2 OP-UU
[348]
Auto Arm Cancellation auto arm cancelled O/C (4) A5 CE-00
[348]
Special Opening Opening (disarming) using one of the following
methods: keyswitch, maintenance code, DLS
software, wireless key
O/C (4) AA OP-00
[349-350]
Battery Trouble/Rest. Main panel battery is low/battery restored Maint. (3) A2 YT-00/YR-00
[349-350]
AC Failure
Trouble/Rest.
AC power to control panel is disconnected or
interrupted/AC power restored (both codes
follow AC Failure transmission delay)
Maint. (3) A1 AT-00/AR-00
[349-350]
Bell Circuit
Trouble/Rest.
open/short circuit detected across bell
terminals/bell circuit restored
Maint. (3) 21 UT-99/UJ-99
[349-350]
Fire Trouble/Rest. a trouble occurs/restores in a fire zone Maint. (3) 73 FT-00/FJ-00
[349-350]
Auxiliary Power
Trouble/Rest.
aux voltage supply trouble/restoral Maint. (3) AA YP-00/YQ-00
[349]
TLM Failure telephone line monitoring trouble (sent via
LINKS. Do not program if LINKS not used)
Maint. (3) 51 LT-00
[350]
TLM Restore Telephone line trouble restore Maint. (3) 51 LR-00
[349-350]
General System
Trouble/Rest.
"Service Required" trouble occurs (view
troubles using [*][2][3])/trouble restored
Maint. (3) AA YX-00/YZ-00
[349-350]
Gen System
Supervisory
Trouble/Rest.
control panel loses/restores communications
with module(s) connected to the Keybus
Misc. (3) 33 ET-00/ER-00
[351]
Line 1 or 2 FTC
Restoral
control panel has restored communications to
central station on line 1or 2
Misc. (3) 54 YK-00
[351]
Event Buffer is 75%
Full
event buffer is almost full Misc. (6) 23 JL-00
[351]
DLS Lead In downloading session start (initiated by panel) Misc. (4) 11 RB-00
[351]
DLS Lead Out downloading session complete Misc. (4) 12 RS-00
[351]
General Zone
Trouble/Rest.
one or more zones have trouble/trouble
restored
Misc. (3) 72 UT-00/UJ-00
[351]
Delinquency programmed amount of time (days or hours) for
delinquency has expired without zone activity
or without system being armed
Misc. (4) 54 CD-00
[352]
Periodic Test periodic sytem test transmission Test (6) A2 RP-00
[352]
System Test [*][6] bell/communications test Test (6) A1 RX-00
[352]
LINKS Test LINKS test transmission Test (6) A3 TX-00
[353]
General Device Low
Battery Trouble/Rest.
Wireless zones/pendants/handheld
keypads/wireless keys have low battery
Test (3) 84 XT-00/XR-00
* A/R = alarms/restorals; T/R = tamper/restorals; O/C = openings/closings; Maint. = maintenance;
Misc. = miscellaneous; Test = test transmission
** UU = user number (access codes 01-42); ZZ = zone number (01-32)
Program the Contact ID Fail to close event code [(4)54] to report either closing or activity delinquency. Make sure your central