2.8. DIAGNOSTICS AND MAINTENANCE
2.9. CABINET
2.9.1. Modular design enables exible installation
2.9.2. Forced air cooling for maximum reliability
2.9.3. All systems are self contained and require external battery cabinet (s)
2.5.1. Emergency power provides FULL LIGHT OUTPUT from all lamps and xtures for the entire runtime
2.5.2. Operates uorescent, compact uorescent, incandescent, quartz, H.I.D., LED and other lamp types
2.5.3. Standard or electronic ballasts, dimming devices or panels, sensors and most control equipment
2.5.4. Standard or LED Exits and other safety equipment
2.6.1. Meet UL 924, NFPA 101, NFPA 70, NEC and OSHA standards
2.6.2. Cities of Chicago and New York approved
2.6.3. Complies with the Buy American Act
2.7.1. Provides overload, surge and undercurrent protection using DSP/PWM technology to protect system perfor-
mance and reliability
2.7.2. Surge protection against load surges as dened in ANSI/IEEE C62.45 category A and B
2.5. LAMPS AND LOADS
2.6. CODES
2.7. PROTECTION
Title: Micro
Doc No.: 018-1000-02
Description: Emergency Lighting Inverter Users Manual Date: 07/26/2016
Rev: NR
1.877.DSPM.POWERPhone : 1.877.377.6769-
909.930.3335Fax:
www.dspmanufacturing.com
Website:
techsupport@dspmanufacturing.com
E-Mail:
19
2.8.1. DSP/PWM technology provides complete self diagnostic capabilities and LED Monitoring
2.8.2. Informative advanced Display and Alarms keep you in control of your emergency lighting environment 24/7
2.8.3 Automatically performs periodic self-tests ensuring a safely lighted environment prior to an emergency. The
power supplies are able to do a 5 minute battery run the rst of every month except for New Year’s day when the test
is for 90 minute. The testing can be enabled by going to the Autorun screen and selecting Yes or No with the Menu
Forward or Menu Reverse button. When the battery test happens the rec tier is turned off, and the batteries will
sustain the load on the output. If the voltage dips too low the test is terminated prematurely, and a entry is recorded
in the alarm log accordingly. Two minutes into the battery run test the voltage, power date, and time are logged in the
battery log. This is a feature that is standard in our power supplies.
2.8.4. Single point of testing instead of multiple testing points with battery packs
2.8.5. Water Dots are placed on every shelf and door panel to indicate if moisture is present or has got inside the unit.
The Dots are originally white in color but will turn red when water is absorbed.
Title: Three Phase 208 or 208Y/120Vac
Doc No.: 018-6000-00
Description: Emergency Lighting Inverter User’s Manual
Rev: NR
Date: 08/12/2022
Phone :
Website:
E-Mail:
Fax:
1.877.DSPM.POWER-1.877.377.6769
1.877.DSPM.POWER-1.877.377.6769
www.dspmanufacturing.com
techsupport@dspmanufacturing.com

Related product manuals