Rev. 10/98 21 949-1239-3
CFSP Communications Fail Set Point (992): Set to desired value.
Addr Control Address (992): Set from 1 to FF. This number (hexadeci-
mal, base 16) must match the address number used by the host
computer. Viewed only in this menu.
SECURE MENU
Hold UP ARROW & ENTER for 5 Seconds. Press INDEX to change the
lower display. Press UP ARROW or DOWN ARROW to change the value
in the upper display.
SECr Security Code: See the Security Level Selection and the Pass-
word Table in this manual, in order to enter the correct password.
InP Input Type: Select one of the following. The Inputs are based on
four different groups; Thermocouples, RTDs, Current, and Volt-
age. If changing from one of these groups, the DIP switch on the
A/D circuit board will have to be changed to match that particular
group. Refer to the Input wiring section for the proper switch
settings.
J-IC Type J Thermocouple
CA Type K Thermocouple
E- Type E Thermocouple
t- Type T Thermocouple
L- Type L Thermocouple
n- Type N Thermocouple
r-13 Type R Thermocouple
S-10 Type S Thermocouple
b- Type B Thermocouple
C- Type C Thermocouple
P392 100 ohm Platinum (NIST 0.00392 //°C), Love
Cal. 104.
n120 120 ohm Nickel, Love Cal. 105.
P385 100 ohm Platinum (DIN 0.00385 //°C), Love Cal.
106.
Curr DC Current Input 0.0 to 20.0 or 4.0 to 20.0 milliam-
peres.
UoLt DC Voltage Input 0.0 to 5.0 or 1.0 to 5.0 volts.
---- Reserved
OSUP Zero Suppression: Select On or OFF. Only with Current and
Voltage input types.
OFF The input range will start at 0 (zero) Input.
On The input range will start at 4.00 mA or 1.00 V.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dwyer Instruments Love Controls 1600 Series and is the answer not in the manual?

Dwyer Instruments Love Controls 1600 Series Specifications

General IconGeneral
BrandDwyer Instruments
ModelLove Controls 1600 Series
CategoryControl Unit
LanguageEnglish

Related product manuals